北京馬駒橋綠色數據中心
Beijing Majuqiao Data Center
一線城市運營商級數據中心
Customized Cloud Computing Data Center for China Telecom Beijing Branch
北京馬駒橋綠色數據中心坐落于北京市南六環路外緣,至CBD僅18公里,緊鄰京滬高速,設計等級Uptime Tier III、新國標A級,于2015年7月投入運行,主要服務于中國電信北京分公司及京津冀地區大型互聯網企業。
Beijing Majuqiao Data Center is located on the outer edge of Beijing South 6th Ring Road, only 18km from Central Business District, near Beijing-Shanghai highway. Its design level is Uptime Tier III, equivalent to grade A of the new national standard. Its main customers are Beijing Branch of China Telecom and large internet companies in Beijing, Tianjin and Hebei since it opened in July 2015.
機房特色
Features
-
為充分利用空間、最大化提高能效,公司設計團隊采用三維技術對各類基礎設施、集裝箱、制冷管道、電纜橋架等進行綜合設計,最終使用1.3萬平方米建筑空間交付近3000個機柜,堪稱數據中心空間布局的成功典范。
In order to fully utilize space and maximize improving energy efficiency, The design team made comprehensive designs for infrastructures, containers, cooling pipelines, cable bridges etc. with 3D technique. Beijing Majuqiao Data Center delivered 3,000 cabinets with 13,000m2 building area, which is regarded as a successful data center space layout model.
-
2015年11月,北京馬駒橋綠色數據中心因首次大規模應用水蓄冷技術轉移數據中心晝夜用電負荷,預計可轉移晝間負荷3894KW,被北京市發展改革委員會列入“北京市電力需求側管理城市綜合試點項目”,為一線城市數據中心的節能建設樹立了標桿和示范。
In November 2015, Beijing Majuqiao Data Center was listed in “Beijing Electricity Demand Side Management City Comprehensive Pilot Project” by Beijing Development and Reform Commission for applying chilled water technique on a large scale to transfer data center electricity load, which can transfer power of 3894KW in day. It has set an example and demonstration for first-tier city data center’s energy saving.
-
2015年12月,北京馬駒橋綠色數據中心入選工業和信息化部辦公廳、國家機關事務管理局辦公室、國家能源局綜合司等三部門聯合發布的首批《國家綠色數據中心試點地區名單》,成為全國84個國家級綠色數據中心試點項目之一。
In December 2015, Beijing Majuqiao Data Center was listed in “National Green Data Center Pilot Area List” issued jointly by 3 departments -- General Office of Ministry of Industry and Information Technology, Office of National Government Offices Administration, Comprehensive Division of National Energy Administration and became one of 84 National Green Data Center Pilot Projects.
建設參數
Construction Parameters
北京市通州區馬駒橋鎮金橋科技產業基地景盛中街38號院
No. 38 Jingsheng Middle Street, Goldenbridge Science and Technology Industrial Base, Majuqiao Town, Tongzhou District, Beijing
|
兩棟聯排,鋼筋混凝土框架結構體系
2 terraced buildings, ferroconcrete frame structure
層高一層5.3m、二層4.8m
Story height: 1st floor: 5.2m, 2nd floor: 4.8m
地板承重8-16KN/㎡
Loading capacity: 8-16KN/㎡
專用貨運電梯及貨物卸載區,貨梯載重2噸
Freight elevator (2 tons), loading bay
|
雙路供電,總供電容量25000KVA
Dual paths, power capacity of 25,000KVA
部分機房UPS系統2N冗余配置,其他N+1,滿載后備供電15分鐘
Some DC rooms with 2N redundant UPS system, others N+1; UPS battery backup time at rated load: 15 minutes
柴油發電機采用N+1冗余設置,市電中斷后1分鐘內供電,滿載后備供電16小時
Diesel generator with N+1 redundant configuration, power supply in 1 minutes after electricity cut, operating 16 hours without refueling
單機柜電力13~20A;局部可按需改造
Each rack power: 13~20A, and could be expanded partially
|
機房使用精密空調調節室內溫度和濕度
Precision air-conditioners control IDC temperature and humidity
空調系統采用UPS電源供電,空調冗余N+1
N+1 redundant air-conditioning system powered by UPS
地板下送風,上回風;冷通道封閉(冷熱通道嚴格隔離)
Down-flow air supply, up-flow air return, enclosed cold passages (cold and hot passages are isolated)
水冷,給水中斷的情況下系統12小時的正常運行;蓄冷罐2-3小時不間斷制冷
Water cooling system operates 12 hours without water supply; cold storage tanks provide 2-3 hours’ cooling in case chillers fail
|
采用IG541自動氣體滅火系統
IG541 automatic gas fire-fighting system
分區相互獨立,可以實現分區滅火,另配備手持式滅火器及空氣呼吸器
Independent zone for fire-fighting separately, each zone equipped with handheld extinguishers and air-breathers
消防與空調、新風、門禁、計算機供電和市電等系統聯動
Linked air-conditioning system, air system, access control system, computer power system, city power system etc.
|
視頻監控系統,另可根據用戶需求定點增加高清攝像設備
Monitoring cameras; HD cameras could be added as needed on spot
授權門禁系統、紅外探測、電子圍欄
Access control system, infrared detection, electronic fences
人員權限設置,設備安全管理,多層安全防范與管理
Staff permission setting, devices safety management, multi-levels security protection
|
中國電信等
Backbone network link to China Telecom etc.
多線均萬兆對接,可隨時根據實際需求進行擴容
Tens of gigabit multiline access, scalable as needed
提供144芯裸纖資源
144 core bare fiber resource
|
7×24小時值守,5分鐘內響應,15分鐘內應急處理反饋
7×24 hours guarding, quick response in 5 minutes, emergency processing and feedback in 15 minutes
擁有完備的應急方案、完善的應急管理流程,切實保障業務連續性
Complete emergency solutions and emergency management process to guarantee business continuity
|
上一篇:無
下一篇:常州鐘樓數據中心